Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/08/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/06/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) WATER LINE AT DRYER VENT MUST BE A MINIMUM 12" AWAY FROM VENT SEE MANUFACTURERS INSTRUCTIONS 2) PROTECT ELECTRICAL WIRE WITH BANG PLATES WITHIN 1 1/4 FROM EDGE OF STUD 3) PROTECT WATER LINES AT KITCHEN PONY WALL WITH BANG PLATE FRONT 4) REPLACE FIRE BLOCK AT KITCHEN WALL TO MASTER BEDROOM WHERE VENT AND WATER LINES PASS THROUGH 5) ELECTRICAL WIRE HANGING AT MASTER BATH |