Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/26/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/24/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 03/21/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SHUT OFF VALVE REQUIRED UPSTREAM AND WITHIN 36" OF GROUND UNION ON GAS LINE 2) ABS PLASTIC VENTS ON ROOF MUST BE PAINTED WITH LATEX PAINT 3) WATER HEATER T&P LINE MUST EXHAUST DOWN 4) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 5) GAS LINE MUST BE ELECTRIC BONDED WITH #4 BOND WIRE 6) NON ? D CIRCUIT BREAKER CANNOT BE IN PANEL 7) FILL ALL CLEANOUTS IN SERVICE PANEL 8) DOUBLE WIRES ON ONE CIRCUIT BREAKER NOT ALLOWED 9) KITCHEN PENSULA MUST HAVE GFCI OUTLET 10) ALL KITCHEN COUNTER OUTLETS MUST BE GFI 11) SMOKE DETECTORS MUST BE INNER CONNECTED TO TRIP ALL WHEN ONE GOES OFF 12) LIVING ROOM REQUIRES SMOKE DETECTORS |