Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM00499

Parcel: 129133820


Addresses:

1132 E 35TH ST #02

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/26/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
03/24/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
03/21/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) SHUT OFF VALVE REQUIRED UPSTREAM AND WITHIN 36" OF GROUND UNION ON GAS LINE 2) ABS PLASTIC VENTS ON ROOF MUST BE PAINTED WITH LATEX PAINT 3) WATER HEATER T&P LINE MUST EXHAUST DOWN 4) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 5) GAS LINE MUST BE ELECTRIC BONDED WITH #4 BOND WIRE 6) NON ? D CIRCUIT BREAKER CANNOT BE IN PANEL 7) FILL ALL CLEANOUTS IN SERVICE PANEL 8) DOUBLE WIRES ON ONE CIRCUIT BREAKER NOT ALLOWED 9) KITCHEN PENSULA MUST HAVE GFCI OUTLET 10) ALL KITCHEN COUNTER OUTLETS MUST BE GFI 11) SMOKE DETECTORS MUST BE INNER CONNECTED TO TRIP ALL WHEN ONE GOES OFF 12) LIVING ROOM REQUIRES SMOKE DETECTORS