Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM00490
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
10/02/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) INSTALL BOND BUSHING ON OFFSET NIPPLES FOR METER/DISCONNECT HOUSE PANEL 2.) BOND BUSINGS REQUIRED FO RISER CONDUITS AT CT CAN 250-94 NEC. 3.) MC CABLE TO BE SUPPORTED WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS PER NEC. |