Permit: T02CM00490

Parcel: 13312006M

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/04/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
10/02/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) INSTALL BOND BUSHING ON OFFSET NIPPLES FOR METER/DISCONNECT HOUSE PANEL 2.) BOND BUSINGS REQUIRED FO RISER CONDUITS AT CT CAN 250-94 NEC. 3.) MC CABLE TO BE SUPPORTED WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS PER NEC.