Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/04/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 10/02/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL BOND BUSHING ON OFFSET NIPPLES FOR METER/DISCONNECT HOUSE PANEL 2.) BOND BUSINGS REQUIRED FO RISER CONDUITS AT CT CAN 250-94 NEC. 3.) MC CABLE TO BE SUPPORTED WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS PER NEC. |