Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2002 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
IVRS - Inspection 0000* |
| 03/18/2002 |
ELECTRIC - TEMP POWER FOR TEST |
|
Partial Approval |
IVRS - Inspection 0000*1. PLEASE INSTALL REJECTON PINS. 2. WE HAVE TRIPPLE LUGGING AT SERVICE DISCONNECT. 110-14. 3. PLEASE CORRECTLY IDENTIFY ISOLATED GROUND WITH YELLOW STRIP. 4. PLEASE HAVE ENGINEER DETERMINE WHAT IS NEEDED FOR ISOLATED GROUND. PLANS DO NOT REFLECT THIS INSTALLATION. 5. FINISH MAKE-UP IN CEILING. |