Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/22/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/20/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) CLIP BOTTOM OF CROSS BRACE NEXT TO FURNACE 2) DRAINAGE SYSTEM NEEDS FILLING FOR TEST 3) BLOCK LAUNDRY DUCT BOOT 4) FIRE BLCOK NEXT TO ENTERTAINMENT CENTER 5) TIE IN TOP PLATES AT ENTRY DOOR AND ENTERTAINMENT CENTER 6) FILL PLUBMIGN CUTS AT KITCHEN BOTTOM PLATE 7) TIGHTEN H.D. AT PATIO DOOR 8) NAIL OFF TC CLIPS 9) BANG PLATE REAR DINING WALL ELECTRIC 10) REAR TRUSS CLIPS ARE WRONG 11) SHIM TRIMMERS AND HEADERS |