Permit: T02CM00409

Parcel: 11010024D


Addresses:

3040 N SWAN RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM00409

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000* STRAP PVC MIN 4' ON HORIZONTAL RUNS. MOVE SMOKE DETECTORS TO RETURN PLENUMS OK FOR SHEET ROCK.
03/01/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) DUCT SMOKE DETECTORS GO IN THE RETURN NOT SUPPLY. 2.) PROVIDE CONDENSATE DRAINS AS PER PLANS. 3.) VERIFY WHAT TYPE OF INSULATION TO USE ON DUCT WORK. OK FOR ONE SIDE OF SHEET ROCK ON WALLS.