Permit: T02CM00366

Parcel: 13612833A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM00366

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
05/21/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) NEED TO SEE WATER HEATER VENT FINISHED 2.) PROVIDE MIN 1" CLEARANCE AROUND WATER HEATER FLUE PIPE. 3.) CONDENSOR FOR FREEZER OVERFUSED. 20 AMP IS MAX. FUSE SIZE 4.) SUPPORT REFER LINES ON ROOF. 5.) RAISE WATER HEATER VENT 2' ABOVE AIR INTAKE ON AC UNIT.