Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM00366
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
05/10/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* CORRECTION REQUIRED 1.) 2 X 4 DROP IN FIXTURES SEISMIC WIRES ARE REQUIRED TO BE ATTACHED AT OPPOSITE "CADDY" CORNERS. TWO 2 PER FIXTURE. 2.) EACH RECESSED LIGHT FIXTURES MUST HAVE A SEISMIC WIRE ATTACHED. 3.) SUPPORT WIRES FOR CONDUITS OR CABLES (MC) MUST BE TIED TO GRID. THIS IS TO PREVENT SWINGING. 4.) REMOVE TAPE (BLUE) SECURING M.C TO EMT AND OR OTHER CALBES. DO NOT SUPPORT CONDUIT FROM CONDUIT OR CABLE ETC. INSTALL SEPARATE SUPPORT WIRE FOR THIS. 5.) INSTALL SEISMIC WIRE TO EVERY EXIT LIGHT MOUNTED IN CIELING. THANKS |