Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM00366

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
05/10/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* CORRECTION REQUIRED 1.) 2 X 4 DROP IN FIXTURES SEISMIC WIRES ARE REQUIRED TO BE ATTACHED AT OPPOSITE "CADDY" CORNERS. TWO 2 PER FIXTURE. 2.) EACH RECESSED LIGHT FIXTURES MUST HAVE A SEISMIC WIRE ATTACHED. 3.) SUPPORT WIRES FOR CONDUITS OR CABLES (MC) MUST BE TIED TO GRID. THIS IS TO PREVENT SWINGING. 4.) REMOVE TAPE (BLUE) SECURING M.C TO EMT AND OR OTHER CALBES. DO NOT SUPPORT CONDUIT FROM CONDUIT OR CABLE ETC. INSTALL SEPARATE SUPPORT WIRE FOR THIS. 5.) INSTALL SEISMIC WIRE TO EVERY EXIT LIGHT MOUNTED IN CIELING. THANKS