Inspection History: BUILDING - FINAL
Permit Number - T02CM00355
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |