Permit: T02CM00286

Parcel: 117071420


Addresses:

646 S 3RD AV #02


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T02CM00286

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/05/2003 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) NEED SPECIAL INSPECTION CERTIFICATE FOR RASTA WALL SYSTEM COMPLETED
02/04/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) OUTSIDE OUTLET CANNOT BE ON BATHROOM GFCI CIRCUIT 2) ALL COUNTER OUTLETS IN KITCHEN MUST BE GFCI PROTECTED (BY STOVE AND ISLAND) 3) BAR BULB LIGHT FIXTURES NOT ALLOWED IN CLOSET 4) SUB PANEL MUST HAVE AN ISOLATED NEUTRAL