Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/05/2003 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NEED SPECIAL INSPECTION CERTIFICATE FOR RASTA WALL SYSTEM COMPLETED |
| 02/04/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) OUTSIDE OUTLET CANNOT BE ON BATHROOM GFCI CIRCUIT 2) ALL COUNTER OUTLETS IN KITCHEN MUST BE GFCI PROTECTED (BY STOVE AND ISLAND) 3) BAR BULB LIGHT FIXTURES NOT ALLOWED IN CLOSET 4) SUB PANEL MUST HAVE AN ISOLATED NEUTRAL |