Permit: T02CM00284

Parcel: 13337017C


Addresses:

10315 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T02CM00284

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) OK FOR DRYWALL.
07/11/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999* 1.) CAN NOT HAVE ANY THREADED FITTINGS IN A CONCEALED LOCATION ON 2" VENT 2.) URINAL STARTS OUT WITH 3" TRAP ARM THEN REDUCES TO 2" THIS TRAP ARM MUST BE 2" STARTING AT THE BARREL. 3.) NO CLOSET RINGS INSTALLED 4.) NO VENTS FLASHING ON 5.) LOOSE COPPER DROPS IN PLBG. WALL. 6.) 4" C.O. IS BEHIND WATER CLOSET TANK 7.) LAVATORY TRAP ARM 90 MUST BE L-SWEEP. 8.) OK TO DRYWALL ALL ROOM EXCEPT PLBG. WALL IN RESTROOM.
07/03/2002 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* NOT READY FOR INSPECTION
07/03/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) AIR PRESSURE TEST ON WATER DISTRIBUTION IS OK 3.) OK TO DRYWALL UPON BLDG. INSPECTOR APPROVAL. 4.) NOTE: THIS INSPECTION IS FOR INTERMEDIATE PLBG. FROM GRID LINE 2 EAST TO GRID LINE #4. AND GRID LINE A SOUTH TO E AND FROM E WEST TO HYDEANT.