Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/24/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 08/02/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* 1.) NEED TO CHECK CONNECTION TO PHOTO SIGN AND EXH. FAN FEED OFFICE AREA. |
| 08/01/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/29/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245* NOTES 1.) SUPPORT EMT CONDUIT WITHIN 3" OF TERMINATION EXCEPT PER EXCEPTION. PER 348 NEC. 2.) NEED TO SEE GAS PIPING BOND. 250-104 NEC. 3.) DO NOT USE RACEWAY TO SUPPORT RACEWAYS 300-11B NEC. |
| 07/08/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* NOTES OK BATHROOMS EMPLOYEE LOUNGE, DRIVE THRU. |