Permit: T02CM00284

Parcel: 13337017C


Addresses:

10315 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM00284

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
08/02/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* 1.) NEED TO CHECK CONNECTION TO PHOTO SIGN AND EXH. FAN FEED OFFICE AREA.
08/01/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
07/29/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* NOTES 1.) SUPPORT EMT CONDUIT WITHIN 3" OF TERMINATION EXCEPT PER EXCEPTION. PER 348 NEC. 2.) NEED TO SEE GAS PIPING BOND. 250-104 NEC. 3.) DO NOT USE RACEWAY TO SUPPORT RACEWAYS 300-11B NEC.
07/08/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* NOTES OK BATHROOMS EMPLOYEE LOUNGE, DRIVE THRU.