Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM00284
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
08/02/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* 1.) NEED TO CHECK CONNECTION TO PHOTO SIGN AND EXH. FAN FEED OFFICE AREA. | |
08/01/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
07/29/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* NOTES 1.) SUPPORT EMT CONDUIT WITHIN 3" OF TERMINATION EXCEPT PER EXCEPTION. PER 348 NEC. 2.) NEED TO SEE GAS PIPING BOND. 250-104 NEC. 3.) DO NOT USE RACEWAY TO SUPPORT RACEWAYS 300-11B NEC. | |
07/08/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* NOTES OK BATHROOMS EMPLOYEE LOUNGE, DRIVE THRU. |