Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/22/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
|
| 02/22/2002 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*TEST OK ON UNDERGROUND SOIL SUBJECT TO APPROVED REVISED PLAN PLEASE PROVIDE REVISED PLAN BY NEXT INSP. |
| 02/07/2002 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NO CHANGE FROM LAST INSP. |
| 02/06/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE APPROVED TRANSISSION FITTINGS FROM ABST. CI. SHIELDED BANDS. 2.) UNCOVER ALL NEW WASTE LINES. 3.) INSTALL ALL WORK TO APPROVED PLAN. REMOVE FITTING NOT TO CODE 1/4 BENDS SANTEE ECT SEC SEC 706.0 CHANGE IN DIRECTION. 4.) PROVIDE WATER TEST ON COMPLETE SYSTEM. 5.) BACKPITCH ON TRUNK LINE. PLEASE EXPOSE PROVIDE 1/4" PER FOOT ON 3" ABS. |