Permit: T02CM00276

Parcel: 11618340A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM00276

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/16/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) LETTER FROM ENGINEER ARCHITECT ASK FOR RICI FUSES ALSO WE NEED REJECTION PINS. 2.) PLEASE TIGHTEN ALL LOCK NUTS AND SECURE ENCLOUSERS TO THE STRUCTURE 3.) WE CAN NOT USE SHEET METAL SCREWS AND CLEAN SURFACE BEHIND LUGS. 4.) PLEASE USE ANTI OXIDE COMPOUND WITH ALUMIUM CONDUCTORS.
04/12/2002 ELECTRIC - FINAL Partial Approval 1. PLEASE INSTALL ALL BONDING DEVICES AT SERVICE 250-94. 2.) FINISH BONDING AT GUTTER. 3.) FINISH INSTALLING REJECTION PINS AND CORRECT FUSES NEED ALL RATINGS AND FAULT CURRENT.
04/11/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*