Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM00276
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
04/16/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) LETTER FROM ENGINEER ARCHITECT ASK FOR RICI FUSES ALSO WE NEED REJECTION PINS. 2.) PLEASE TIGHTEN ALL LOCK NUTS AND SECURE ENCLOUSERS TO THE STRUCTURE 3.) WE CAN NOT USE SHEET METAL SCREWS AND CLEAN SURFACE BEHIND LUGS. 4.) PLEASE USE ANTI OXIDE COMPOUND WITH ALUMIUM CONDUCTORS. | |
04/12/2002 | ELECTRIC - FINAL | Partial Approval | 1. PLEASE INSTALL ALL BONDING DEVICES AT SERVICE 250-94. 2.) FINISH BONDING AT GUTTER. 3.) FINISH INSTALLING REJECTION PINS AND CORRECT FUSES NEED ALL RATINGS AND FAULT CURRENT. | |
04/11/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |