Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/11/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 04/04/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) WE NEED BONDING DEVICES AT THE SERVICE PER 250-94. 2. PLEASE BOND GUTTER 250-96. 3.) MAIN BONDING JUMPERS TO BE SIZED PER 250-102,250-66. 4.) WE CAN NOT USE SHEETMETAL SCREWS FOR GROUNDING 250-8. 5.) PLEASE PROVIDE REJECTION PINS FOR DISCONNECTS 6.) FINISH SUPPORTING ALL CONUITS AS PER CODE. 7.) POWER WILL BE RECEASED UPON FINAL OF EACH SPACE. |
| 03/20/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* SERVICES TO BE INSTALLED AS PER CODES. |