Permit: T02CM00272

Parcel: 11618340A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM00272

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/10/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection MEET WITH ELECTRICAN AND REVIEWED PROJECT OPENED SOME WALLS FOUND WE NEED REPAIRS AS PER LAST INSPECTION. PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD FOR VERIFICATION OF L-11 CONTRACTOR.
03/08/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999* 1.) SUPPORT ALL CABLE WITH 12" OF EVERY BOX 2.) USE CORRECT LABEL CONNECTORS FOR MC THESE LOOK LIKE ROMEX CONNECTORS. 3.) WALLS COVERED WITH OUT INSPECTION 4.) NAME OF LICENSED ELECT CONTRACTOR L-11. 5.) ALL ELECTRICAL BOXES COVERED WITH OUR INSPECTION TO BE OPENED. 6.) HAVE ELECTRICAL CONTRACTOR MEET WITH INSPECTOR CALL 791-5550 EXT 136 7-8AM ON DAY OF REQUESTED INSPECTION. CALL ONE DAY AHEAD FOR MEETING.