Permit: T02CM00261

Parcel: 122154490

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/27/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) PLBG FINAL IS OK
2.) OK FOR C OF O.
11/25/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) URINAL REQUIRE A C.O.
2.) SEE NOTE #4 AS REQUESTED 3.) SEE NOTE #2.
11/21/2002 PLUMBING - FINAL Cancelled IVRS - Ri canceled
11/13/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST INSULATE C.W. LINES @ EXTERIOR SOFTENER. 2.) MUST PROVIDE VACCUM BREAKERS @ ALL HOSE BIBS.
3.) MUST RUN P & T DRAIN TO DAYLIGHT FOR BOILER.
4.) MUST PROVIDE TRAP PRIMER FOR FUNNEL DRAIN.
5.) H.C. COUNTER TOP S CAN ONLY BE 34" AFF MAX SEE RESTROOM ELEVATIONS MENS & WOMENS.
6.) 3" C.O. IN MENS RM REQUIRES 18" OF CLEARANCE TO FRONT OF C.O.
7.) WOMENS WATER CLOSET REQUIRES 15" SIDE CLEARANCE.
8.) MUST USE SCREW CAP OR PLUG FOR KITCHEN C.O.
9.) ADA URINAL MAX IS 17" AFF.