Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) PLBG FINAL IS OK 2.) OK FOR C OF O. |
|
| 11/25/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) URINAL REQUIRE A C.O. 2.) SEE NOTE #4 AS REQUESTED 3.) SEE NOTE #2. |
|
| 11/21/2002 | PLUMBING - FINAL | Cancelled | IVRS - Ri canceled | |
| 11/13/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) MUST INSULATE C.W. LINES @ EXTERIOR SOFTENER. 2.) MUST PROVIDE VACCUM BREAKERS @ ALL HOSE BIBS. 3.) MUST RUN P & T DRAIN TO DAYLIGHT FOR BOILER. 4.) MUST PROVIDE TRAP PRIMER FOR FUNNEL DRAIN. 5.) H.C. COUNTER TOP S CAN ONLY BE 34" AFF MAX SEE RESTROOM ELEVATIONS MENS & WOMENS. 6.) 3" C.O. IN MENS RM REQUIRES 18" OF CLEARANCE TO FRONT OF C.O. 7.) WOMENS WATER CLOSET REQUIRES 15" SIDE CLEARANCE. 8.) MUST USE SCREW CAP OR PLUG FOR KITCHEN C.O. 9.) ADA URINAL MAX IS 17" AFF. |