Permit: T02CM00261

Parcel: 122154490

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
06/21/2002 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection 0000*OK TO CLEAR TEMP POWER FOR CONST. ONLY ENERGIZED POWER OUTSIDE UNTIL INSPECTIONED
06/20/2002 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0245*NOTES 1.) BONDING DEVICE NEEDS TO BE INSTALLED ON CT CAN RISER CONDUIT. 250-94. NEC. 2. INSTALL BOND BUSHINGS WHERE USING CONCENTRIC KO'S ON SERVICE DISCONNECTS PER ART 250 NEC. 3.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE.