Permit: T02CM00231

Parcel: 11307012A


Addresses:

1717 E GLENN ST

Inspection Status: Not Applicable

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
01/19/2007 ELECTRIC - CONSTRUCTION POWER Not Applicable IVRS - Inspection :*
01/17/2002 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection 0000*
01/16/2002 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0245*NOTES 1.) INSTALL PERMANENT ADDRESS LABEL. 2.) MAIN BREAKER MUST BE RATED 22K 3.) PLACE 2ND GROUND ROD IN TRENCH.