Permit: T02CM00208

Parcel: 123110270


Addresses:

1034 E LESTER ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM00208

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2002 FRAMING Approved IVRS - Inspection 0000*
08/27/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SECURE ELECTRIC 6" FROM BOXES 2) BLOCK MECHANICAL AIR RETURN 3 SIDES 3) PROVIDE WATER TEST ON DWV SYSTEM 5) STRAP OR CLIP INTERIOR BEARING WALL AT RIDGE BEAM SUPPORT
08/13/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) BLOCK DEFUSER BOOTS 3 SIDES 2) PEX PLUMBING NOT ALLOWED WITHIN 12" OF RECESSED LIGHTS 3) FIREBLOCK FURRED OUT WALL AT MASONARY WALL TOP 4) BATH DUCT NOT CONNECTED 5) SUPPORT NORTH END OF RIDGE BEAM 6) BEDROOM WINDOWS MUST HAVE RELEASABLE SECURITY BARS 7) SUPPORT 1" GAS LINE AT 10' ON CENTER 8) GAS LINE MUST BE ELECTRICALLY BONDED IN EXPOSED LOCATION WITH #4 WIRE 9) FIRE STOP RANGE CHASE 10) PROVIDE 22 X 30 ATTIC ACCESS 11) PROVIDE A/C CONDENSATE DRAIN 12) WATER HEATER T&P LINE MUST EXHAUST OUTSIDE 13) NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF WALL SURFACE