Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T02CM00208

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
07/02/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) COLLAR TIE OVER BUILD AT 4' ON CENTER 2) PORCH POST REQUIRE EPC FROM BEAM TO POST 3) NAIL ROOF AND WALL SHEATHING AT 6" ON CENTER ON SUPPORTED ENDS, EDGES AND 12" IN FIELD 4) CROSS BRACE 3 GABLE END TRUSSES FROM RIDGE TO BOTTOM CHORD