Permit: T02CM00191

Parcel: 122180630


Addresses:

1617 N WINSTEL BL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/25/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) GAS SHUT OFF VALVES OK 2.) GAS PRESSURE TEST OK 3.) WATER HTR FLU VENT, P&T DRAIN & VALVE IS OK 4.) GA PACK ON ROOF OK.
01/24/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*MUST REMOVE UNION IN LINE ON ROOF AND REPLACE WITH RIGHT & LEFT HAND NIPPLE 2.) RETEST SYSTEM.