Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM00191

Parcel: 122180630


Addresses:

1617 N WINSTEL BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/26/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
01/23/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NOTES 1.) WHERE PVC CONDUIT IS INSTALLED EXPOSED IT MUST BE SCH 80 2.) LOAD CENTERS ON OUTSIDE WALLS NOT TO BE USED AS J-BOXES USE LISTED J-BOX. 3.) INTERIOR REMODEL AND CIRCUITING FOR OUTSIDE NOT REFLECTED ON PRESENT JOB PLAN .4.) RE SUBMIT ACCURATE PLAN AND OBTAIN PERMIT FOR WORK BEING DONE. PER RICHARD VIDAL. ALSO WORK TO BE DONE BY L-11 C-11 LICENSED CONTRACTOR. NEED VERIFICATION PLEASE. 5.) ALSO SEPERATE NEUTRALS AND GROUNDS IN OUTSIDE PANELS FOR EACH UNIT NEUTRALS AND GROUNDS ARE ALREADY BONDED AT MAIN DISCONNECT ENCLOSURE.