Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/26/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 01/23/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) WHERE PVC CONDUIT IS INSTALLED EXPOSED IT MUST BE SCH 80 2.) LOAD CENTERS ON OUTSIDE WALLS NOT TO BE USED AS J-BOXES USE LISTED J-BOX. 3.) INTERIOR REMODEL AND CIRCUITING FOR OUTSIDE NOT REFLECTED ON PRESENT JOB PLAN .4.) RE SUBMIT ACCURATE PLAN AND OBTAIN PERMIT FOR WORK BEING DONE. PER RICHARD VIDAL. ALSO WORK TO BE DONE BY L-11 C-11 LICENSED CONTRACTOR. NEED VERIFICATION PLEASE. 5.) ALSO SEPERATE NEUTRALS AND GROUNDS IN OUTSIDE PANELS FOR EACH UNIT NEUTRALS AND GROUNDS ARE ALREADY BONDED AT MAIN DISCONNECT ENCLOSURE. |