Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM00179
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/20/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) PROVIDE NORTH WEST PROPERTY PIN 2) SEVERAL GE CIRCUIT BREAKERS NOT COMPATABLE WITH BRYANT SERVICE PANEL 3) LABEL ALL CIRCUITS IN ELECTRIC PANEL 4) ABS PLUMBING NOT ALLOWED EDPOSED BELOW ROOF ON EXTERIOR OF BUILDING 5) ALL OUTLETS ON KITCHEN COUNTER MUST BE GFCI PROTECTED 6) SEVERAL OVER FILLED CONDUITS TO MANY TO LARGE OF WIRES 7) CLOTHES WASHER/DRYER MUST BE ON A 3 WIRE PROVIDED CIRCUIT-PRESENTLY ON 2 WIRE GROUNDED 8) FLEXABLE NON METALIC CONDUIT CANNOT PENETRATE METAL WATER HEATER CABINET 9) OPEN ALL ELECTRIC BOXES AND REMOVE ALL SWITCHES AND OUTLETS FOR INSPECTION 10) RANGE MUST BE ON A 3 WIRE GROUNDED CIRCUIT |