Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM00179

Parcel: 124091280

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM00179

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2002 FRAMING Approved IVRS - Inspection 0000*
08/20/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE NORTH WEST PROPERTY PIN 2) SEVERAL GE CIRCUIT BREAKERS NOT COMPATABLE WITH BRYANT SERVICE PANEL 3) LABEL ALL CIRCUITS IN ELECTRIC PANEL 4) ABS PLUMBING NOT ALLOWED EDPOSED BELOW ROOF ON EXTERIOR OF BUILDING 5) ALL OUTLETS ON KITCHEN COUNTER MUST BE GFCI PROTECTED 6) SEVERAL OVER FILLED CONDUITS TO MANY TO LARGE OF WIRES 7) CLOTHES WASHER/DRYER MUST BE ON A 3 WIRE PROVIDED CIRCUIT-PRESENTLY ON 2 WIRE GROUNDED 8) FLEXABLE NON METALIC CONDUIT CANNOT PENETRATE METAL WATER HEATER CABINET 9) OPEN ALL ELECTRIC BOXES AND REMOVE ALL SWITCHES AND OUTLETS FOR INSPECTION 10) RANGE MUST BE ON A 3 WIRE GROUNDED CIRCUIT