Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T02CM00163
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2002 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*1.) ABS DWV UNDERGROUND OK WATER TEST OK 2.) GREASE TRAP OK 3.) TIE IN TO EXISTING OK TRANSITION FITTINGS OK 4.) OK TO BACKFILL. | |
03/27/2002 | PLUMBING - ROUGH, SOIL | Denied | 1.) HORIZONTAL VENTING BELOW FLOOD LEVEL OF FIXTURE LIMITED TO STRUCTURAL CONDITIONS 2.) CLEAN OUTS FOR BRANCH PIPING OVER 5' FROM MAIN TO BE FULL SIZED. 3.) MINIMUM TRAP ARM LENGTH FROM WEIR OF TRAP TO POINT OF VENT TO BE MINIMUM 2 PIPE DIAMETERS 4.) NO FLOOR CLEAN OUT OR VENT ON GREASE TRAP. 5.) ALL SINKS REQUIRE CLEAN-OUTS 6.) BLAKETEES ARE NOT APPROVED ON THEIR BACK, UNDERGROUND FOR TESTING USE APPROVED DIRECTIONAL FITTINGS. |