Permit: T02CM00163

Parcel: 137055220


Addresses:

1217 W IRVINGTON RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T02CM00163

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) ABS DWV UNDERGROUND OK WATER TEST OK 2.) GREASE TRAP OK 3.) TIE IN TO EXISTING OK TRANSITION FITTINGS OK 4.) OK TO BACKFILL.
03/27/2002 PLUMBING - ROUGH, SOIL Denied 1.) HORIZONTAL VENTING BELOW FLOOD LEVEL OF FIXTURE LIMITED TO STRUCTURAL CONDITIONS 2.) CLEAN OUTS FOR BRANCH PIPING OVER 5' FROM MAIN TO BE FULL SIZED. 3.) MINIMUM TRAP ARM LENGTH FROM WEIR OF TRAP TO POINT OF VENT TO BE MINIMUM 2 PIPE DIAMETERS 4.) NO FLOOR CLEAN OUT OR VENT ON GREASE TRAP. 5.) ALL SINKS REQUIRE CLEAN-OUTS 6.) BLAKETEES ARE NOT APPROVED ON THEIR BACK, UNDERGROUND FOR TESTING USE APPROVED DIRECTIONAL FITTINGS.