Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/31/2009 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 01/17/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) SUPPORT CONDUIT ABOVE PANEL AS PER CODE AND ALONG THE ROOF 2.) AN APPROVED FITTING NEED TO BE USED ABOVE PANEL AND AT LB. ALSO THEY NEED TO BE WEATHER PROOF. 3.) SEALTITE FITTING NEED TO BE LISTED FOR USE AS APPLIED. 4.) PLEASE PROTECT CONDUCTOR WHERE PASSING THROUGH ENCOUSERS. 5.) APPROVED SEALING DEVICES ARE REQUIRED TO FILL UNUSED OPENINGS. 6.) PLEASE VERIFY WHO LICENSED ELECTRCIAL CONTRACTOR IS DOING THE WORK. |