Permit: T02CM00136

Parcel: 136310260

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM00136

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
06/12/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*SECURE MC CABLE PER N.E.C. INSTALL FHA PLATE WHERE MC CABLE IS WITHIN 1 1/4" FROM FRONT EDGE OF STUD. UNCOVER TRENCH W/PVC TO VERIFY DEPTH FOR REQ'D INSPECTION SEAL OPEN K.O. AT HANDY BOX.