Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/14/2002 |
PLUMBING - FINAL |
|
Approved |
1.) PLBG FINAL IS OK 2.) ALL CORRECTIONS HAVE BEEN MADE 3.) OK FOR C OF O. |
| 02/13/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE OPEN FRONT SEAT LESS LID FOR H.C. WATER CLOSET. 2.) H.C. WATER CLOSET REQUIRES HANDLE TO BE ON OPEN SIDE OF RM (AA SPECS.) 3.) MUST WRAP LAVATORY WASTE & SUPPLYS 4.) MUST PROVIDE GRID STRAINERS FOR H.C. LAV & HAND SINK 5.) 2" C.O. BY WATER HTR MUST HAVE 12" CLEARANCE FROM FRONT OF C.O. 6.) MUST CAULK AND SECURE SERVICE SINK AND CAULK TRIPLE COMP SINK. 7.) MUST SECURE GAS LINE DROP FOR SINGLE BURNER STOVE. |
| 02/11/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) DOORS LOCKED. |