Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 01/28/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) HORIZONTAL WASTE LINE EXCEEDS 135 CHANGE OF DIRECTON WILL REQUIRED A C.O. AFTER THE 1ST 135 2.) SOIL WATER TEST WAS DOWN. 3.) P-3 IS A MOP SINK AND IS A 2 FIXTURE UNIT FUXTURE. THIS FIXTURE WILL REQUIRE A 2" DRAIN MIN. 4.) NO P&T DRAIN INSTALLED @ THIS TIME 5.) CAN NOT MIX MATCH MATERIALS ON WATER DISTRIBUTION. EITHER ALL COPPER OR ALL PEX. |