Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T02CM00121

Parcel: 13316037K

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/30/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
01/28/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) HORIZONTAL WASTE LINE EXCEEDS 135 CHANGE OF DIRECTON WILL REQUIRED A C.O. AFTER THE 1ST 135 2.) SOIL WATER TEST WAS DOWN. 3.) P-3 IS A MOP SINK AND IS A 2 FIXTURE UNIT FUXTURE. THIS FIXTURE WILL REQUIRE A 2" DRAIN MIN. 4.) NO P&T DRAIN INSTALLED @ THIS TIME 5.) CAN NOT MIX MATCH MATERIALS ON WATER DISTRIBUTION. EITHER ALL COPPER OR ALL PEX.