Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/19/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/08/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) WINDOW WITHIN 24" OF DOOR WAY MUST BE SAFETY GLAZED 2) COMPRESSION FITTINGS ON 3/4" PEX NOT ALLOWED ENCLOSURE IN WALLS AND CEILINGS IMPROPER CONNECTIONS THROUGHOUT 3) SEAL/BACK GROUT FLOOR UNDER TUB 4) LEAK AT WATER HEATER 5) NO WATER HEATER T&P LINE-MUST EXTEND OUTSIDE 6) INTERMIXING OF PEX PRODUCTS NOT ALLOWED 7) SMOKE DETECTORS MUST BE AT LEAST 36" FROM AIR REGISTERS 8) TOILET MUST HAVE 2" WASTE VENT 9) LAUNDRY NOT VENTED-WASTE TRAP TO HIGH. STRAPED WRONG |
| 07/01/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |