Permit: T02CM00116

Parcel: 10713242L


Addresses:

307 E JACINTO ST

Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Date Description Inspector Results Comments
05/09/2002 BUILDING PRE-SLAB Approved IVRS - Inspection 0000*
05/03/2002 BUILDING PRE-SLAB Denied IVRS - Inspection 0999*/ 1) NO WATER TEST ON SEWER LINES 2) PLANS/PERMITS NOT ON SITE 3) NO ANSWER TO KNOCKING ON DOOR AT 8:45 AM
04/30/2002 BUILDING PRE-SLAB Denied IVRS - Inspection 0999*/ 1) MANY SEWER LINES FITTINGS MISALIGNED AND STRAINED 2) SANITARY "T" FITTINGS CANNOT BE USED IN SEWER OR DRAIN LINES 3) SEWER LINES MUST BE AT LEAST 12" BELOW GRADE AT EXIT OF BUILDING 4) W/C NOT PROPERLY VENTED 5) REDUCING BUSHING CANNOT BE USED IN SEWER OR DRAIN LINE 6) HOLDOWNS REQUIRE REBAR ABOVE HOOK