Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/24/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
04/23/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) NEED 10 FT WATER COLUMN TEST ON ALL D.W.V. 2) TUB TRAP-TOO HIGH-WEIR CANNOT BE ABOVE VENT OPENING 3) UFER GROUND REQUIRED AT SERVICE PANEL #4 CONDUCTOR CONNECTED TO 20' REBAR WITH UFER CLAMP 4) DRAIN CANNOT BE BRIDGED USE CODE 00005 AND 03005 FOR NEXT INSPECTION