Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/28/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ELECTRIC SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR 2) UFER GROUND MUST BE CONNECTED TO ELECTRIC SUB PANEL GROUND BAR 3) PROVIDE PROOF OF PERMIT AND INSPECTION FOR ELECTRIC SERVICE UPGRADE 4) EXPOSE DEPTH OF UNDERGROUND ELECTRIC CONDUIT |