Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM00029
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/28/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1.) SUB-PANEL MISSING COVER 2.) DEVICES IN KITCHEN BY SINK DO NOT FIT PROPERLY IN BOX COVER PLATE NOT INSTALLED 3.) NEW OUTLET PER NOTE-6 NOT INSTALLED NOTE -4. PER ELECT. PLAN. | |
02/06/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TO COVER WALLS 1.) AN APPROVED CONNECTOR IS NEEDED TO ATTACH CABLE TO SWITCH BOX IN BATHROOM 373-5. | |
01/28/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) NM CABLE ABOVE SUBPANEL IS TO BE SECURED 336-18. 2.) AN APPROVED CONNECTOR IS NEEDED TO ATTACHING CABLE TO BOXES. ALSO TIGHTEN BOX CLAMP WHERE SUPPLIED 373-5. 3.) PLEASE PROVIDE GROUND AIL FOR SWITCHES ON ROUGH-IN INSPECTION. 4.) FHA STRAPS WILL BE NEEDED IN CORNERS AND AT NOTCHES TO PROTECT NM CABLE 300-4. 5.) PLEASE ATTACH ALL BOXES TO THE STUDS AND STAPLES WITH IN 12" HAVE A NICE DAY. |