Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM00027
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
08/01/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) ELECTRICAL PANEL CIRCUIT DIRECTORY IS INCOMPLETE 2.) SWITCH BOX AT EXTERIOR NEXT TO REAR DOOR, IS OPEN WITH EXPOSED WIRING. 3.) MC CABLE USED TO WIRE WTR HTR. SHOULD BE WRAPEED WITH 10 MIL VINYL TAPE WHERE IT MAY COME IN CONTACT WITH THE COPPER WATER LINES. 4.) CHANGE IN FRONT DOOR SWING HAS RENDERED THE LIGHT SWITCHES IN ACCESSIBLE ON ENTRY. 5.) ROOF TOP A/C SERVICE SWITCH MUST BE MARKED WITH PANEL AND CIRCUITS FEEDING IT CORRECT RECALL |