Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T02CM00001
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2003 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000* | |
| 11/19/2002 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection 0000*/ 1) FIRST LIFT OF REVISION | |
| 10/30/2002 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection 0215* 1) CANNOT APPROVE SERVICE RELOCATION UNTIL TRENCH IS DRY 2) UFER CANNOT BE SPLICED EITHER HAVE WELDED OR INSTALL 2 GROUND RODS AT LEAST 6 FEET APART CONNECTED TO SERVICE PANEL WITH A CONTINOUS #4 CONNECTION 30 PUT ADDRESS ON PANEL 4) SERVICE RISER NOT BONDED INSTALL BOND BRUSHING |