Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02BU02598

Parcel: 123080460


Addresses:

2728 E HELEN ST

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
12/12/2002 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection 0000*
11/26/2002 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection 0999*/ 1) INSTALL HEATER TEMP/PRESSURE RELIEF 2) WINDOW SCREENS TO HAVE NON-REMOVABLE HEADS 3) REAR DOUBLE DRIVE GATES NOT TO CODE 4) CHAIN LINK FENCE CANNOT BE CLIMBABLE 5) CANNOT VERIFY GAS PIPING UNDER RAISED WOOD FLOOR OF HOUSE (CRAWL-HOLE TO SMALL) 6) GAS LINE NOT RUN PER PLAN 7) MAXIMUM 4" GAP BETWEEN VERTICAL BARS (IRON FENCING) 8) SUPPORT GAS PIPING UNDER FLOOR MAXIMUM 8' SPACING 9) GALVANIZED GAS PIPING TO BE A MINIMUM OF 6" ABOVE GRADE 10) ENCLOSURE NOT TO PLAN OR CODE 11) GATE LATCHES NOT PER CODE 12) SUPPORT ELECTRIC CONDUIT MORE RIGIDLY 13) BLOCK WALL EAST SIDE NOT MINIMUM HEIGHT