Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 02/03/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 01/29/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*NEED BLUE PRINTS ON SITE. |
| 11/12/2002 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*1.TRANSVERSE BARS ("2" BARS,) ARE NOT INPLACE 2.) ARE YOU USING PLAN FOR 8" BLOCK OR PLAN FOR 8/12 COMBO? IF YOU ARE USING PLAN FOR 8/12. COMBO? IF YOU ARE USING PLAN FOR 8" BLOCK THEN I NEED TO BE ABLE TO READ DETAIL FOR 5' WALL. |
| 10/29/2002 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*1.) NO EXCAVATED PER PLAN. 2.) REINFORCEMENT NOT PER PLAN. 3.) YOUR FOOTING NEEDS TO BE 3'6" WIDE (42") FOR 6' RETAINING. FOOTING NEEDS TO BE 12" THICK. 4 EACH #4 HORIZONTALS REQUIRED. YOU HAVE NO TRANVERSE BARS IN PLACE. |