Permit: T02BU02295

Parcel: 123071280


Addresses:

2132 E MABEL ST

Inspection Status: Approved

Inspection History: POOL/SPA PRE-GUNITE

Date Description Inspector Results Comments
05/22/2003 POOL/SPA PRE-GUNITE Approved IVRS - Inspection 0000*
09/24/2002 POOL/SPA PRE-GUNITE Partial Approval IVRS - Inspection 0000*/ 1) ELECTRIC SERVICE ENTRANCE CABLE LOCATED IN VIOLATION OF NEC 680.8 ELECTRIC SERVICE PANEL APPROX 6 1/2 FEE FROM POOL WITH INSULATED CONDUCTORS APPROX 14 FEET ABOVE GRADE. RELOCATE SERVICE ENTRANCE CABLES OUTSIDE 10' FROM POOL PRIOR TO FINAL INSPECTION (WATER)
09/17/2002 POOL/SPA PRE-GUNITE Not ready for Inspection IVRS - Inspection 0000*/ 1) SVR-CHARGE ON POOL WALL/WEST PUT ENGINEERS STAMPED REBAR SCHEDULE ON PLANS, STAMPED BY CITY OF TUCSON 2) YOU DON'T HAVE 22' FROM POOL TO OVER HEAD CONDUCTORS 3) UNSEALED METER AT SERVICE OVER HEAD CONDCUTORS TEMP CONNECTED