Permit: T02BU02046

Parcel: 111022900


Addresses:

3830 N BORG LN

Inspection Status: Approved

Inspection History: POOL/SPA PRE-GUNITE

Date Description Inspector Results Comments
09/06/2002 POOL/SPA PRE-GUNITE Approved IVRS - Inspection 0000*
09/05/2002 POOL/SPA PRE-GUNITE Denied IVRS - Inspection 0935*/ 1) ITEMS 1, 2 AND 4 FROM 8/22/02 INSPECTION NOT COMPLIED WITH 2) INSPECTION OF 8/29/02 NOT COMPLIED WITH. YOU MUST PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION 3) NOTE: WINDOW ON NORTH EAST CORNER OF HOUSE IW SITHIN 5 FEET OF POOAN DN MUST BE SAFETY GLAZED BY FINAL INSPECTION
08/29/2002 POOL/SPA PRE-GUNITE Not ready for Inspection IVRS - Inspection 0000*ITEMS LISTED FROM 1ST INSP. HAVENT BEEN APPROVED. 2.) PLEASE NOTE ON PLAN THE WALL DETAIL YOU USED.
08/22/2002 POOL/SPA PRE-GUNITE Denied IVRS - Inspection 0999*/ 1) POOL HEATER HAS VALVES BETWEEN INLET/OUTLET AND POOL, REQUIRES TEMP PRESSURE RELIEF VALVE 2) HEATER NOT BONDED 3) POOL REQUIRES 3 FEET TO SOUTH PROPERTY LINE ONLY 2'-6" EXISTS AND WEST SET BACK 4) FREE STANDING WALL REQUIRES #3 BARS AT 6" ON CENTER EACH WAY SEE 4/S-1 AND 1/S-2 5) CONDUIT OK-WIRES NOT IN