Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/30/2002 |
POOL/SPA PRE-GUNITE |
|
Approved |
IVRS - Inspection 0000*OK TO GUNITE. |
| 07/25/2002 |
POOL/SPA PRE-GUNITE |
|
Denied |
IVRS - Inspection 0999*/ 1) GAS PRESSURE TOO LOW FOR TEST-7 POUNDS AT INSPECTION 2) METAL COMPRESSION FITTINGS ON GAS LINE MUST BE COMPLETELY TAPED 3) ALL COMPRESSION FITTINGS MUST BE VISIBLE FOR INSPECTION. OK TO BACKFILL ALL ELSE 4) PROVIDE TPR VALVE ON HEATER OR MANUFACTURERS SPECS STATING OTHERWISE 5) BOND BEAM BETWEEN SPA AND POOL IS INADEQUATE IN BOTH SIZE AND MOUNT OF STEEL-PER DETAIL #6 |