Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T02BU01960
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2002 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection 0000* | |
10/24/2002 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection 0000* 1) FENCE GROUNDING OK 2) GAPS CLOSED TO 4" OK 3) SWING SLIDE IN NEIGHBORS YARD MOVED OK 4) GATE TO POOL DOES NOT CLOSE PROPERLY NOT OK | |
10/22/2002 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection 0810*/ 1) METAL FENCE WITHIN 5' OF POOL EDGE MUST BE ELECTRICALLY BONDED TO POOL EQUIPMENT WITH A #8 BONDWIRE 2) GAPS IN METAL FENCE EXCEED 4" AT 45 DEGREE CORNER 3) SWING SLIDE IN NEIGHBORS YARD MUST BE 4' FROM PARTY WALL POOL BARRIER |