Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date |
Description |
Inspector |
Results |
Comments |
| 10/25/2002 |
POOL/SPA FINAL/BARRIER |
|
Approved |
IVRS - Inspection 0000* |
| 10/24/2002 |
POOL/SPA FINAL/BARRIER |
|
Partial Approval |
IVRS - Inspection 0000* 1) FENCE GROUNDING OK 2) GAPS CLOSED TO 4" OK 3) SWING SLIDE IN NEIGHBORS YARD MOVED OK 4) GATE TO POOL DOES NOT CLOSE PROPERLY NOT OK |
| 10/22/2002 |
POOL/SPA FINAL/BARRIER |
|
Denied |
IVRS - Inspection 0810*/ 1) METAL FENCE WITHIN 5' OF POOL EDGE MUST BE ELECTRICALLY BONDED TO POOL EQUIPMENT WITH A #8 BONDWIRE 2) GAPS IN METAL FENCE EXCEED 4" AT 45 DEGREE CORNER 3) SWING SLIDE IN NEIGHBORS YARD MUST BE 4' FROM PARTY WALL POOL BARRIER |