Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2002 |
POOL/SPA FINAL/BARRIER |
|
Approved |
IVRS - Inspection 0000* |
| 09/30/2002 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000* TALKED TO THE JOB ELECTRICIAN, LAST INSPECTION ALL ITEMS HAVE NOT BEEN ADDRESSED |
| 09/26/2002 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) ANTI-SIPHON INSTALLED HORIZONTALLY, LEAVE INFO FOR THIS DEVICE 2) NEED MAIN BREAKER FOR SERV. MAX 6 SIWTCHES 3) NEED INSULATED #8 BOND WIRE, AND APPROVED J-BOX |
| 09/04/2002 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NON-METALLIC CONDUIT TO BE 18" BELOW NEUTRAL GRADE MINIMUM, UNCOVER AND LOWER JOINT TO BE 6" ABOVE GRADE 2) ALL METAL WITHIN 5' OF POOL WATER TO BE BONDED BACK TO MOTOR, (PUMP) 3) YOU NEED POOL FENCE BOND BOTH SIDES OF GATE 4) G.E. SERVICE PANEL, USE ONLY G.E. BREAKERS 5) NO MAIN IN SERVICE, MAXIMUM SIX SWITCHES WITHOUT A MAIN 6) LEAVE INSTALLATION INFORMATION FOR ANTI-SYPHON DEVICE OR INSTALL IN VERTICAL POSITION 7) FENCE CHAIN LINK TO WROUGHT IRON GAP NO MORE THAN 4", TIE TOGETHER SO THE CHAIN LINK CANNOT BE PUSHED BACK 8) INSTALL AN APPROVED J-BOX FOR POOL LIGHT 9) INSTALL A #8 INSULATED GROUND WIRE INSIDE. WET NICHE FIXTURE EN CAPSULATE CONNECTION IN POOL CAN AND AT J-BOX CONDUIT WITH APPROVED POTTING COMPOUND |