Permit: T02BU01830

Parcel: 14026003L

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
11/12/2002 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection 0000*
11/08/2002 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*1.) C3 F4 FOOTING ON LINE A CAST WITHOUT INSPECTION.
2.) ANCHORS IN SAME FOOTINGS "WET SET" WITHOUT CONSOLEDATION OF CONCRETE.
3.) LOADING DOCK @ A3.5
CAST WITHOUT INSPECTION.
10/23/2002 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*NO APPROVED PLANS AVAILABLE OFFICE LOCKED.
10/01/2002 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*F5 & F6 FOOTING LINE A
09/27/2002 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*TILT UP PANELS COMPLETE. AND NORTH WEST & SOUTH FOOTING PERIMETER.
09/24/2002 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*
09/20/2002 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*HAVE ALL BARS IN PLACE PER DETAIL 6,7 & 5 PAGE 54.1. IE 3 #6 EACH FACE 4" O.C. AT LOWER SECTION. HIGH PANELS ALOS CANTILEVER PANELS REQUIRE #6 EACH FACE AT TOP.
09/13/2002 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*CANCELLED BY CONTRACTOR.
09/12/2002 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*NO NEW WORK SINCE LAST INSPECTION.
09/10/2002 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*TILT PANELS 13,16,18,19,21,22,24,25,26,30,31, OK TO POUR. 2.) PANELS 23 & 28 NOT READY NEED 2 #'S WELDED TO WELD PLATE PER DETAIL 230. TERRACON REPORT OK THESE PANELS IS INVALID.
09/04/2002 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*LINE 4,B,D,E,F, COL. FOOTERS PER 116/55.1
08/28/2002 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*
08/01/2002 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*C1 F2 FOOTING 10 EACH INTERIOR. 1.) I NEED COMPACTION REPORTS. 2.) KEEP ALL SPECIAL INSPECTION REPORTS @ JOB SITE. SPECIAL INSPECTION REPORTS FOR STEEL, WELDING ETC ARE REQUIRED TO BE HERE AND AVAILABLE BEFORE I BEGIN MY INSPECTION.
07/25/2002 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*1.) PROVIDE ENGINEERED SOIL PLACEMENT AND COMPACTION REPORTS 2.) CLARIFY WHICH OF THE LISTED SPECIAL INSPECTIONS ARE REQUIRED FOR THIS JOB PAGE 51.1. PROVIDE SPECIAL INSPECTION FIELD REPORT FOR ALL REQUIRED SPECIAL INSPECTIONS DURING THE COURSE OF THIS JOB. 3. HAVE ANCHOR BOLTS READY.