Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02BU01458

Parcel: 119217160

Inspection Status: Approved

Inspection History: MODULAR - ELECTRIC INSPECTION

Date Description Inspector Results Comments
09/23/2002 MODULAR - ELECTRIC INSPECTION Approved IVRS - Inspection 0000*
09/17/2002 MODULAR - ELECTRIC INSPECTION Denied IVRS - Inspection 0999*ACORN CLAMP ON SOUTH GROUDING ELECTRODE NOT INSTALLED PER LISTING. 2.) GROUNDING ELECTRODE RODS SHOULD BE DRIVEN INTO EARTH THEY MAY ONLY BE LAYED IN DITCH WHEN TERRAIN DOES NOT ALLOW FOR DRIVING THEM IN 3.) SERVICE RISER NOT PROPERLY BONED TO GROUND. LOCK NUTS.