Inspection Status: Approved
Inspection History: MODULAR - ELECTRIC INSPECTION
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2002 |
MODULAR - ELECTRIC INSPECTION |
|
Approved |
IVRS - Inspection 0000* |
| 09/17/2002 |
MODULAR - ELECTRIC INSPECTION |
|
Denied |
IVRS - Inspection 0999*ACORN CLAMP ON SOUTH GROUDING ELECTRODE NOT INSTALLED PER LISTING. 2.) GROUNDING ELECTRODE RODS SHOULD BE DRIVEN INTO EARTH THEY MAY ONLY BE LAYED IN DITCH WHEN TERRAIN DOES NOT ALLOW FOR DRIVING THEM IN 3.) SERVICE RISER NOT PROPERLY BONED TO GROUND. LOCK NUTS. |