Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date |
Description |
Inspector |
Results |
Comments |
| 09/11/2002 |
POOL/SPA FINAL/BARRIER |
|
Approved |
IVRS - Inspection 0000* |
| 08/09/2002 |
POOL/SPA FINAL/BARRIER |
|
Denied |
IVRS - Inspection 0999*/ 1) IRC SECTION E.4106.9.2, OR NEC SECTION 680-20 AND #1 PLEASE READ ONE OR BOTH OF THESE SECTIONS, FROM THESE CODE BOOKS 2) #8 INSULATED BOND WIRE SEE LAST 3 INSPECTIONS 3) REINSPECTION FEE DUE BEFORE NEXT INSPECTION |
| 08/01/2002 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) MISSING #8 INSULATED BOND WIRE A LIGHT JUNCTION BOX. 3RD TIME I HAVE BEEN HERE FOR THIS ITEM? |
| 07/03/2002 |
POOL/SPA FINAL/BARRIER |
|
Denied |
IVRS - Inspection 0999*1.) REINSPECTION FEE DUE BEFORE NEXT INSP. 2.) DONT USE POOL LIGHT. 3.) POOL FILLED WITHOUT FINAL 4.) H2O & ELECT NOT AT CORRECT DEPTH AT HOUSE. |
| 07/01/2002 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) FROM LAST INSPECTION FOR ITEMS 08030 AND 08035 FILL LINE FEEDER, CONDUIT FROM SERVICE POINTS, UNCOVER FOR INSPECTION 2) MISSING #8 INSULATED BAND FROM LIGHT TO J-BOX, J-BOX IS INCOMPLETE POTTING COMPOUND BONDING |
| 06/28/2002 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NO WAY INTO REAR YARD 2) PLEASE LEAVE DIRECTIONS FOR NEXT INSPECTION |