Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/09/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*ELECTRICAL FINAL APPROVED TO OPERATE (SUBJECT TO OTHER INSPECTOR) MUST HAVE COPY OF REVISION DELIEVERED TO 201 N. STONE FOR CITY STAMP. |
| 04/19/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 04/11/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 04/11/2002 |
ELECTRIC - FINAL |
|
Denied |
WILL REQUIRE A TERMINAL STRAP FASTENED INSID THE P.V.C BOX TO TERMINATE ALL EQUIPMENT GROUNDS NEED GROUNDING BUS HINGE AND BONDING JUMPERS THROUGH-OUT. 2.) NEED WELDED CONDUIT ENTRIES INTO LIGHT POLE 3.) NEED TERMINAL STRIP FOR WEATHER PROOF BOX SEE #1 AT 30 AMP DISCONNECT AREA. A EQUIPMENT GROUND LUG INSTALLED WITH SHEET METAL SCREWS. B THE TERMINAL BAR CONTAINING THE NEUTRAL IS BONDED TO THE ENCLOSURE C WEATHER PROOF BOX SEE #3. D THE NEUTRAL AT 30 AMP DISCONNECT MUST ALSO BE DISCONNECTABLE. |
| 04/09/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
|