Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T02BU00859
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2002 | ELECTRIC - UNDERGROUND | Approved | ||
04/18/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*REVISE PLAN ON UNDERGROUND CONDUIT NOW ENTERING EXIST. POLE LITE JUNCTION BOX INSTEAD OF A DIRECT PATH TO THE DISCONNECT SWITCH LOCATED ADJACENT TO E STOP. HAVE ENGINEER STAMP. REVISE PLANS. HAVE ENGINEER STAMP FOR THE APPROVAL OF USING LIGHT POLE CONDUIT, AND LIGHT POLE AS JUNCTION BOX TO REACH THE AREA OF THE DISCONNECT SWITCH BY E STOP | |
04/01/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*1.) CANNOT USE TELEPHONE BOOTH AS A JUNCTION BOX. 2.) PROJECT MUST BE DONE AS PER PLAN. DO NOT COMBINE BOOTH CIRCUIT WITH PROPANE CIRCUIT. 3.) WILL NEED A DISCONNECT SWITCH FOR PROPANE PER PLAN. 4.) EMERGENCY SWITCH WILL BE OPERABLE TO SHUNT TRIP ALL. SHOW ON REVISED PLAN IF YOU ARE RERISING. OTHER CONDUIT INSTALL ALL SEALS OFF. |