Permit: T02BU00748

Parcel: 136403350

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
03/29/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
03/26/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*THE WORK IS INCOMPLETE 1.) WHAT IS REBAR FOR? REMOVE 2.) MOVE GROUND ROD AWAY FROM UNDER PEDESTAL. 3.) TERMINATE "UFER" GROUND ON LUG FURNISHED UNDER CKT. BRKR'S. 4.) COMPLETE THE CONNECTION TO THE STORAGE SHED. 5.) COMPLETE THE LOCAL 20 AMP. GFI RECP. INSTALL. 6.) REMOVE ANY UNUSED WIRES.