Inspection History Details
Inspection Status: Approved
Inspection History: MODULAR - ELECTRIC INSPECTION
Permit Number - T02BU00007
Inspection Description - MODULAR - ELECTRIC INSPECTION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2002 | MODULAR - ELECTRIC INSPECTION | Approved | IVRS - Inspection 0000*OK TO CLEAR ELEC. FINAL TEMP PED. | |
03/15/2002 | MODULAR - ELECTRIC INSPECTION | Denied | IVRS - Inspection 0999*"AGAIN!!" PROVIDE A MIN. 36" DEPTH X 30" WIDTH IN FRONT OF THE MODULAR PER ART. 110-26 1999 NATIONAL ELECTRIC CODE. PLEASE CORRECT TO AVOID A REINSPECTION FEE NEXT TIME. | |
03/13/2002 | MODULAR - ELECTRIC INSPECTION | Denied | IVRS - Inspection 0999*1.) PROVIDE MIN. 36" WORKING CLEARANCE IN FRONT OF THE MODULAR SUB-PANEL (PER 110-26 N.E.C.) |