Permit: T02BU00007

Parcel: 141303330

Inspection Status: Approved

Inspection History: MODULAR - ELECTRIC INSPECTION

Permit Number - T02BU00007

Inspection Description - MODULAR - ELECTRIC INSPECTION

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2002 MODULAR - ELECTRIC INSPECTION Approved IVRS - Inspection 0000*OK TO CLEAR ELEC. FINAL TEMP PED.
03/15/2002 MODULAR - ELECTRIC INSPECTION Denied IVRS - Inspection 0999*"AGAIN!!" PROVIDE A MIN. 36" DEPTH X 30" WIDTH IN FRONT OF THE MODULAR PER ART. 110-26 1999 NATIONAL ELECTRIC CODE. PLEASE CORRECT TO AVOID A REINSPECTION FEE NEXT TIME.
03/13/2002 MODULAR - ELECTRIC INSPECTION Denied IVRS - Inspection 0999*1.) PROVIDE MIN. 36" WORKING CLEARANCE IN FRONT OF THE MODULAR SUB-PANEL (PER 110-26 N.E.C.)